Tank Supervision Library

The tank supervisor library provides a number of common functions inherent to oilfield stock tank monitoring and control by Wago PFC200 controllers.

Tank SupervisorFeature Summary

Fluid Height Calculations Configurable Inputs Accepts “top only” or “top + interface” gaugers
Conversion to trucker units Converts decimal feet to feet/inches/quarters and feet/inches/eights
Fluid Volume Calculations Supports linear conversion bbl/ft factor
Supports tank strapping tables Up to ten (10) strapping tables
Supports multiple instances Multiple, equalized instances can be treated as a single “Tank”
Strapping tables User-created Create in EXCEL and save as .csv
Load onto PLC Use free BLT software to load strapping table onto PLC
Gauger Reading Filters Statistical Minimizes impact of spurious gauger readings
Configurable Filter time window is adjustable depending upon gauger update rate (e.g., wireless)
Automatic Loadout Detection Configurable filtering Specify minimum loadout volume and minimum outflow rate
Loadout history archived on PLC Each completed loadout is stored in persistent file system
Automatic data retention feature maintains history for user-specified number of days
Loadout Accumulations Loadout Volume Today, Yesterday, Current Month, Previous Month - per tank
Global, configurable gauge-off hour applies to all tanks
Loadout Summary Use free BLT software to copy loadout files from PLC and build a summary file (on a PC) of loadouts from history
Pump Controllers Interface Support Works in conjunction with HOA switch and (optional) permissive
Control Algorithm (HOA) HAND=on, OFF=off, AUTO=automatic algorithm
Automatic Algorithm Pump latched on when high threshold is exceeded. Pump stops when low threshold is crossed
Configurable Dynamic configuration of high threshold, low threshold, and source tank
Library Capacity Configured through host program (to minimize memory footprint) Up to 254 tanks, up to 254 controllers
Up to 10 tank strapping tables (fixed maximum)
Configurable number of tank strapping table rows (for optimum memory use)
Licensing Free for developer Library file is free and can be added to any Wago e!COCKPIT instance
Runtime Licensed Library generates a site code on the PLC
Beyond HMI, Inc. generates a license file from site code
License file is installed on the PLC. License is perpetual but only usable on that PLC.
Library features will execute for about 4 days after restart in trial mode. License must be installed before this period expires or data will be lost (unrecoverable).

Licensing

The BhiLibTank library is available at no cost to e!COCKPIT users. The library uses runtime licensing. A license is required for each PLC which executes the library code. The program will run for approximately 4 days in trial mode before a license is required. Licenses must be purchased from Beyond HMI, Inc.